Strip footings

How wide, thick and deep a strip footing must be for a single-storey house on class C, H, R and S sites.

What a strip footing is

A strip footing (the standard also calls it a strip foundation) is a long, flat strip of concrete laid in the bottom of a trench. The wall is built on top of it. Its job is to spread the weight of the wall over a wider strip of ground, so the ground under it is not overstressed (A.3.1). SANS 10400-H describes it as a rectangular concrete foundation, unreinforced or lightly reinforced, that supports masonry walls (definition 3.44). Masonry means walls built of bricks or blocks laid in mortar.

Cross-section through a strip footing, showing the footing below natural ground level, the wall on top, and the floor above ground
Cross-section through a strip footing, showing the footing below natural ground level, the wall on top, and the floor above ground

When the standard sizes apply

The sizes in this lesson are the standard's ready-made answers. They only apply to a certain kind of building. If the house falls outside these limits, the foundations must be designed by a competent person instead.

The ready-made strip footing sizes are for single-storey type 1 masonry buildings. A type 1 masonry building is one with masonry walls that are not held up by columns of steel, concrete or reinforced masonry, and that is not used for storage or industry (definition 3.48). An ordinary single-storey brick house is the typical example.

The building must also stay inside these limits (4.3.2.1.1):

  • walls no higher than 5,0 m from floor level to the top of a gable;
  • roof trusses or rafters spanning no more than 8,0 m between supporting walls;
  • a roof covering (other than a concrete roof) weighing no more than 80 kg per square metre;
  • foundation walls no higher than 1,5 m, and fill under floor slabs no deeper than 1,0 m.

There are also limits on the span and thickness of concrete roof slabs (4.3.2.1.1(c) and (e)).

The sizes below are for class C, H, R and S sites: the plain classes, without a 1, 2 or 3 after the letter (4.3.2.2). For H1, C1 and S1 sites the standard has stricter details (see "Sites with more movement" below).

How wide: Table 3

The minimum width of the footing, often written as w, depends on two things: whether it sits on rock or on soil, and what kind of roof the walls carry (Table 3).

With a tiled or sheeted roof (the usual case):

  • on soil: 400 mm under internal walls, 500 mm under external walls;
  • on rock: 400 mm under both.

With a reinforced concrete roof (a flat concrete slab roof):

  • on soil: 750 mm under internal walls, 600 mm under external walls;
  • on rock: 400 mm under both.

Notice the surprise in the concrete-roof row: the internal walls need the wider footing. The standard does not explain this, but a likely reason is that an internal wall can carry the roof slab from both sides, while an external wall carries it from one side only. The note to Table 3 points the same way: an internal wall that carries no load from the concrete roof may have a 400 mm footing.

An internal wall is a wall inside the house. An external wall is an outside wall of the house.

How thick

A strip footing must be at least 200 mm thick. The only exception is a footing bearing directly onto solid rock: there it only needs to be thick enough to give a level surface to build on (4.3.2.2.1(c)).

How deep

As you saw in the previous lesson, the underside of the footing must be at least 400 mm below natural ground level, except on rock (Figure 5). Natural ground level is the ground surface before any digging.

The first course of bricks

The first layer (course) of bricks on the footing is laid in a bed of mortar. That first bed joint (horizontal mortar joint) must be between 5 mm and 40 mm thick (4.3.2.1.2).

The footings themselves must also be built in line with SANS 2001-CM2, the construction standard for strip footings (4.3.2.1.2).

What concrete to use

Concrete is described by its grade: the number is its strength. Figure 5 labels the plain strip footing as "grade 10 or better". Note 3 under Figure 5 then adds that grade 10 is allowed in unreinforced parts provided it is cured (kept damp while it hardens), but that grade 15 should be used for strip footings and grade 20 for floor slabs.

These two statements are not fully consistent. "Should" usually signals a recommendation rather than a strict requirement, so grade 10 may be acceptable if cured, but grade 15 is what the standard recommends for strip footings. If a question asks about this, read it carefully and check the wording against Figure 5 and its note 3.

Sites with more movement

On H1, C1 and S1 sites, the standard uses modified normal construction: normal construction with extra precautions (4.3.2.4 and Table 4). For the foundations this means wider, deeper and reinforced footings. For external walls 100 mm wide or less, Figures 8 and 10 show footings 600 mm wide under external walls and 450 mm under internal walls, 250 mm thick, made of grade 20 concrete with steel bars, founded at least 500 mm deep unless the geotechnical report says otherwise. The walls also get light reinforcement and joints that allow small movements.

On sites with even more movement (such as H2, H3, C2 and S2, and class P), the foundation must be designed by a competent person. Annex B of SANS 10400-H lists the kinds of solution used, such as deep strip foundations, soil rafts and stiffened rafts.

Key words from this lesson

  • Strip footing: a strip of concrete under a wall that spreads its weight over the ground.
  • w: the width of the footing, from Table 3.
  • Type 1 masonry building: a brick or block building whose walls are not held up by columns, not used for storage or industry.
  • Bed joint: a horizontal layer of mortar between courses of bricks.
  • Modified normal construction: the stricter standard details for H1, C1 and S1 sites.

Clauses This Lesson Cites